6ES7314-1AG13-0AB0

Description: The Siemens Simatic 6ES7314-1AG13-0AB0 is a S7-300 314 CPU with MPI interface integrated. 6ES73141AG130AB0 is a 24 V DC power supply with 96 KBYTE working memory. Micro memory card necessary. Successor number: 6ES7314-1AG14-0AB0

Mô tả

General information
Hardware product version 01
Firmware version V2.6
Engineering with
● Programming package STEP 7 V5.2 + SP1 or higher with HW update
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Input current
Current consumption (rated value) 0.6 A
Current consumption (in no-load operation), typ. 60 mA
Inrush current, typ. 2.5 A
I²t 0.5 A²·s
Power loss
Power loss, typ. 2.5 W
Memory
Work memory
● integrated 96 kbyte; For program and data
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 511; Number range: 1 to 511
● Size, max. 16 kbyte
FB
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 16 kbyte
FC
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 16 kbyte
OB
● Size, max. 16 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 1; OB 20
● Number of cyclic interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 4; OB 80, 82, 85, 87
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset 8
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total All, max. 64 KB
Flag
● Number, max. 256 byte
● Retentivity available Yes; MB 0 to MB 255
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 511; Number range: 1 to 511
● Size, max. 16 kbyte
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 510 byte
Address area
I/O address area
● Inputs 1 kbyte
● Outputs 1 kbyte
Process image
● Inputs 128 byte
● Outputs 128 byte
Digital channels
● Inputs 1 024
— of which central 1 024
● Outputs 1 024
— of which central 1 024
Analog channels
● Inputs 256
— of which central 256
● Outputs 256
— of which central 256
Hardware configuration
Number of expansion units, max. 3
Number of DP masters
● integrated 0
● via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master No
● to DP, slave No
● in AS, master Yes
● in AS, slave No
● on Ethernet via NTP No
Digital inputs
integrated channels (DI) 0
Digital outputs
integrated channels (DO) 0
Analog inputs
integrated channels (AI) 0
Analog outputs
integrated channels (AO) 0
Interfaces
Number of industrial Ethernet interfaces 0
Number of RS 485 interfaces 2
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Point-to-point connection No
MPI
● Number of connections 12
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing No
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD loops, max. 4
● Number of GD packets, max. 4
● Number of GD packets, transmitter, max. 4
● Number of GD packets, receiver, max. 4
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 64 byte
S5 compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication 8
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 8
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— can be set No
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 or higher with HW update
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 280 g